- This topic has 1 reply, 1 voice, and was last updated 4 years, 11 months ago by .
-
Topic
-
Non- Linear loads is more than 50 % of total connected load . Explain the selection of capacitors and also explain the advantages of High and Ultra High duty capacitors.
Non- Linear loads is more than 50 % of total connected load . Explain the selection of capacitors and also explain the advantages of High and Ultra High duty capacitors.
Viewing 1 replies (of 1 total)
Viewing 1 replies (of 1 total)
- You must be logged in to reply to this topic.

Where SrT is the transformer rated power in kVA, and Qc the capacitor rating in kvar, and ukr the rated impedance voltage (in per cent) of the transformer and the feeding network, and v is the number of the highest critical harmonic. REFERENCE: ABB SWITCHGEAR MANUAL